Will Pipe Testing Break My Pool Pipes?

No. The test uses a small fraction of what pool pipes are rated for. It finds damage that is already there; it does not cause it.

(954) 290-5177 Broward (561) 325-2678 Palm Beach

It is a fair question. Nobody wants a test to turn a small problem into a big one. Here are the actual numbers.

Pool pipe and fittings are rated well over 300 psi. Florida code has new pool plumbing tested at 35 psi when it goes in. Our tests stay well under both.

During Pool Leak Detection

On a leak detection, the homeowner owns the pool and the equipment being tested, so we can bring a line up to as much as 25 psi. That is still below the 35 psi new plumbing is tested at, and a tiny fraction of what the pipe can take.

During a Pool Inspection

An inspection is handled more gently. We start with a static test, which uses only the pressure already sitting in the line when the pump is off. If that result is unclear, we may run a low-pressure test, and we keep it at 15 psi or less. That is less pressure than the pool pump puts on the same lines every day it runs.

The reason for the lower limit is the equipment. On inspections we use pneumatic plugs because they are less invasive, and those plugs are not built to hold 25 psi.

What a Failed Test Really Means

A sound pipe holds the test. If a line loses pressure, the crack, separated joint, or weak spot was already there and already leaking or about to. The test simply shows where the problem is so it can be repaired before it gets worse.